Power Systems
An isolated synchronous generator with transient reactance equal to 0.1 pu on a 100 MVA base is connected to the high voltage bus through a step up transformer of reactance 0.1 pu on a 100 MVA base. The fault level at the bus is

 500 MVA
 200 MVA
 400 MVA
 100 MVA

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
The incremental fuel costs for two generating units G1 and G2 are given by Ic1 = 25 + 0.2 PG1 and Ic2 = 32 + 0.2 PG2, where PG1 and PG2 are real powers generated by the units. The economic allocation for a total load of 250 MW, neglecting transmission loss, is given by

 PG1 = 100 MW and PG2 = 150 MW
 PG1 = 142.5 MW and PG2 = 107.5 MW
 PG1 = 109.75 MW and PG2 = 140.25 MW
 PG1 = 125 MW and PG2 = 125 MW

ANSWER DOWNLOAD EXAMIANS APP