Power Systems
A transmission line has a reactance of 1 Pu is operating at Vs = Vr = 1 Pu. The generator is connected at source end which is delivering 0.5 Pu of active power and the transmission line is compensated with a series capacitance of 0.5 Pu. Find the load angle with series capacitance compensation ?

 29°
 14.5°
 35.5°
 10.5°

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
Consider a three phase, 50 Hz, 11 kV distribution system. Each of the conductors is suspended by an insulator string having two identical porcelain insulators. The self capacitance of the insulators is 5 times the shunt capacitance between the link and ground. Find the voltage across the two insulators V1 and V2? (V1 = Voltage of disc nearest to the conductor)

 V1 = 6 kV and V2 = 5 kV
 V1 = 3.46 kV and V2 = 2.89 kV
 V1 = 2.89 kV and V2 = 3.46 kV
 V1 = 5 kV and V2 = 6 kV

ANSWER DOWNLOAD EXAMIANS APP