Power Systems Under over excitation synchronous phase modifier works as shunt capacitor series capacitor any of the above shunt reactor shunt capacitor series capacitor any of the above shunt reactor ANSWER DOWNLOAD EXAMIANS APP
Power Systems A 3 core cable gives on test a capacitance of 3.7 µF between two cores. Find the line charging current of the cable when it is connected to 11 kV, 50 Hz system? 1 A. 1.476 A. 14.7 mA. 14.76 A. 1 A. 1.476 A. 14.7 mA. 14.76 A. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The main objectives of electrical power transmission is/are both 1 and 2 nether 1 nor 2 Voltage regulation of the transmission line must be zero or minimum Transmission system must be more efficient with minimum line losses both 1 and 2 nether 1 nor 2 Voltage regulation of the transmission line must be zero or minimum Transmission system must be more efficient with minimum line losses ANSWER DOWNLOAD EXAMIANS APP
Power Systems The pickup value of relay is 6.5 Amp and fault current in relay coil is 39 Amp. Its plug setting multiplier is 7 A. 10 A. 6 A. 8 A. 7 A. 10 A. 6 A. 8 A. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The per unit impedance Z(pu) is given by ZΩ* (MVA)b/((KV)²b *100) ZΩ* (MVA)b*100/(KV)²b ZΩ* (kVA)b/(KV)²b ZΩ* (MVA)b/(KV)²b ZΩ* (MVA)b/((KV)²b *100) ZΩ* (MVA)b*100/(KV)²b ZΩ* (kVA)b/(KV)²b ZΩ* (MVA)b/(KV)²b ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following method is used for changing power factor from leading to lagging series capacitor shunt capacitor shunt reactor any of the above series capacitor shunt capacitor shunt reactor any of the above ANSWER DOWNLOAD EXAMIANS APP