The line currents in amperes in phases a, b and c respectively are 500 +j150, 100 – j600 and – 300 + j600 referred to the same reference vector with phase sequence of abc. Find the symmetrical component of currents.

Ia₀ = (100+j50) AIa₁ = (200+ j107.75) AIa₂ = (200-j107.75) A
Ia₀ = (100+j50) AIa₁ = (146.41+ j65.47) AIa₂ = (546.41-j165.47) A
Ia₀ = (100+j50) AIa₁ = (546.41+ j165.47) AIa₂ = (546.41-j165.47) A
Ia₀ = (100+j50) AIa₁ = (546.41+j165.47) AIa₂ = (-146.41-j65.47) A

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In a 3-phase, 4-wire, 400/230 V system, a lamp (L1) of 100 W is connected to one phase and neutral and a lamp (L2) of 150 W is connected to the second pahse and neutral. If the neutral wire is disconnected accidently, then

both 100 W lamp (L1) and 150 W lamp (L2) becomes brighter
both 100 W lamp (L1) and 150 W lamp (L2) becomes dim
100 W lamp (L1) becomes brighter and 150 W lamp (L2) becomes dim
100 W lamp (L1) becomes dim and 150 W lamp (L2) becomes brighter

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Consider a solar PV plant with the following specific conditions: Analysis period: 1 year
Measured average solar irradiation intensity in 1 year: 120 kWh/m²
Generator area of the PV plant: 10 m²
Efficiency factor of the PV modules: 15%
Electrical energy actually exported by plant to grid: 110 kWh
Calculate the performance ratio.

0.5111
0.6111
0.8111
0.7111