Power Systems In a 3-phase transmission line, each phase is supported by 3 insulated discs, maximum voltage of each disc is 20 kV. Find the operating voltage of the transmission line per phase if efficiency of string is 80.6%. 20 kV 48.36 kV 52.84 kV 83.76 kV 20 kV 48.36 kV 52.84 kV 83.76 kV ANSWER DOWNLOAD EXAMIANS APP
Power Systems A power station supplies the peak load of 50 MW, 40 MW and 70 MW to three localities. The annual load factor is 0.50 p.u. and the diversity factor of the load at the station is 1.55 the maximum demand on the station and average load respectively will be 57.5 MW. 52 MW. 53 MW. 51.61 MW. 57.5 MW. 52 MW. 53 MW. 51.61 MW. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The neutral of 10 MVA, 11 kV alternator is earthed through a resistance of 5 ohms. The fault ready is set to operate at 0.75 A. The current transformers have a ratio of 1000/5. What is the percentage of the alternator winding is protected? 85% 15% 88.2% 11.8% 85% 15% 88.2% 11.8% ANSWER DOWNLOAD EXAMIANS APP
Power Systems The positive sequence reactance will be equal to negative sequence if the equipment is transformer and transmission lines. none of these. generator. motor. transformer and transmission lines. none of these. generator. motor. ANSWER DOWNLOAD EXAMIANS APP
Power Systems If the conductor diameter decreases, inductance of the line, increases None of these remains unaffected decreases increases None of these remains unaffected decreases ANSWER DOWNLOAD EXAMIANS APP
Power Systems Hydro-graph is similar to load curve. mass curve. both B and C. energy load curve. load curve. mass curve. both B and C. energy load curve. ANSWER DOWNLOAD EXAMIANS APP