Power Systems If the breakdown voltage of the insulator is high, the thickness of the insulator is less high it does not related to breakdown voltage None of these less high it does not related to breakdown voltage None of these ANSWER DOWNLOAD EXAMIANS APP
Power Systems Maximum power capacity of a transmission line can be increased by increasing voltage level nether 1 nor 2 decreasing reactance value either 1 or 2 increasing voltage level nether 1 nor 2 decreasing reactance value either 1 or 2 ANSWER DOWNLOAD EXAMIANS APP
Power Systems What will be the thermal efficiency of a 240 V, 1000 W electric kettle if it brings 2 liters of water at 15° C to boiling point 15 Minutes 80.25 %. 79.33 %. 78.96 %. 74.56 %. 80.25 %. 79.33 %. 78.96 %. 74.56 %. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The charging reactance of 50 km transmission line is 1500 Ω. What is the charging reactance for 100 km length of line? 1500 Ω 1000 Ω 750 Ω 3000 Ω 1500 Ω 1000 Ω 750 Ω 3000 Ω ANSWER DOWNLOAD EXAMIANS APP
Power Systems A loss less transmission line having surge impedance loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30 %. Then SIL of compensated transmission line will be 2280 MW. 1835 MW. 2725 MW. 3257 MW. 2280 MW. 1835 MW. 2725 MW. 3257 MW. ANSWER DOWNLOAD EXAMIANS APP
Power Systems In an induction relay for a particular current setting the operating time 4 sec. When the time multiplier setting is 0.8 if the time multiplier setting is rest to 1 the operating time is 1. 10. 5. un changed. 1. 10. 5. un changed. ANSWER DOWNLOAD EXAMIANS APP