Power Systems
A 25 MVA, 11 kV alternator is supplying full load at a point of 0.75 lagging. Determine the percentage increase in earning capacity when it is operated at improved power factor of 0.96 lagging.

  56 %.
  28 %.
  14 %.
  None of above

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
An hydro-graph indicates

 the discharge at any time during the period under consideration.
All of these
 the average run off during the period.
 the maximum and minimum run off during the period.

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
Consider a three phase, 50 Hz, 11 kV distribution system. Each of the conductors is suspended by an insulator string having two identical porcelain insulators. The self capacitance of the insulators is 5 times the shunt capacitance between the link and ground. Find the voltage across the two insulators V1 and V2? (V1 = Voltage of disc nearest to the conductor)

 V1 = 2.89 kV and V2 = 3.46 kV
 V1 = 6 kV and V2 = 5 kV
 V1 = 3.46 kV and V2 = 2.89 kV
 V1 = 5 kV and V2 = 6 kV

ANSWER DOWNLOAD EXAMIANS APP