A 200/400 V, 20 kVA, 2-winding transformer is connected as an auto-transformer to transform 600 V to 200 V. Calculate the kVA rating of the auto-transformer.
Here auto transformer change voltage from 600 V to 200 V. Voltage ratio (a) = 600/200 = 3 kVA rating of the auto-transformer = (a/(a - 1))*(kVA rating of auto transformer) = (3/2)*20 = 30 kVA
The speed regulation of a motor expresses how much its speed varies between no-load and full load. The synchronous motor runs at a constant speed whose magnitude is dependent on supply frequency and the number of poles. Since the speed of the motor is constant hence its speed regulation is zero. Under no-load conditions with normal excitation, armature current Ia drawn by a synchronous motor lags the applied voltage V by a small angle.
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q
Value of power factor is varies from 0 to 1. R→PF = 1 L→PF = 0 lag C→PF = 0 lead R-L→0 lag < PF < 1 R-C→0 lead < PF < 1 R-C-L→depends on value of R, L and C. PF = R/Z