MGVCL Exam Paper (30-07-2021 Shift 1)
Which type of connection is employed for current transformers for the protection of delta- star connected 3-phase transformer?

delta-star
star-delta
delta-delta
star-star

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Determine maximum permissible load which a 15 MVA, ONAN cooled transformer to IS : 2026 can take for 6 hr, if the initial load on it was 12 MVA. The weighted ambient temperature is 20˚C. Assume the permissible load kVA as a fraction of rated kVA is 1.25.

9.6 MVA
15 MVA
18.75 MVA
12 MVA

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Stability of power system can be improved by
1. Reducing voltage of transmission
2. Using parallel transmission lines
3. Using series compensators
Which of the above statements are correct?

1 and 3 only
2 and 3 only
All 1, 2 and 3
1 and 2 only

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
The single line diagram of the simple system is shown in figure the corresponding reactance diagram is

B
C
A
D

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP