Electrical Machines
Two generators G1 and G2 are to be operated in parallel to deliver a total current of 60 A. Generator one has a terminal voltage of 280 V on no load and 240 V when supplying 40 A current. Similarly the second generator has a voltage of 300 V when on no load and 240 V when supplying of 50 A of current. The output voltage of each generator will be

 238.2 V.
 240 V.
  256.4 V.
 271.7 V.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
The result of slip test on a 3-phase, 20 KVA, 400 V, 50 Hz connected salient pole alternator is given below- Phase value: Vmax = 100 V, Vmin = 96 V, Imax = 10 A and I min = 7 A. The direct and quadranature axis reactances are respectively

 14.28 and 9.60 Ω.
 8.248 and 9.60 Ω.
 8.248 and 5.54 Ω.
  14.28 and 5.54 Ω.

ANSWER DOWNLOAD EXAMIANS APP