The current flowing to a balanced delta connected load through line 'a' is 15 A when the conductor of line 'b' is open. With the current in line 'a' as reference, compute the symmetrical components of the line currents. Assume the phase sequence of 'abc'.
In bias differential protection for transformer, There are two basic settings required to setup the percentage biased differential protection. 1. Minimum pickup 2. The slope.
The minimum pick-up covers the transformer magnetizing current typically 1-4% of transformer rating. A pick up of 0.2 to 0.3 times the TAP is recommended for general cases.
The slope is defined by determining the potential sources of differential current.
Class B trip curve: The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection. Hence, For 16 A current Type B MCB disconnect fault at 3*16 = 48 A to 5*16 = 80 A.
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q