MGVCL Exam Paper (30-07-2021 Shift 2)
A three-phase, 12 kV, 50 Hz and 300 kW load is operating at 0.8 pf lag. If the pf is to be improved to unity, using star connected capacitor, the per phase value of the reactive VAR required is:

50 kVAR
100 kVAR
75 kVAR
25 kVAR

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A given solar cell has the following specifications:
Open-circuit voltage, Voc: 0.7 V
Short-circuit current, Isc: 3 A
Voltage at maximum power, Vmp: 0.5 V
Current at maximum power, Imp : 2.65 A
Calculate the fill factor.

1.23
0.81
1.58
0.63

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
The voltage applied to a transformer primary is increased keeping V/f constant. With this, the core loss ____ and the magnetizing current (Im) ____

remains constant, decreases
decreases, increases
increases, increases
increases, remains constant

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP