Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q
For lagging power factor = (IR*cosφ + Ixsinφ)/Vr For leading power factor = (IR*cosφ - Ixsinφ)/Vr Zero voltage regulation occurs on leading power factor only.
Carrier current over the power line provides simultaneous tripping of circuit breakers at both ends of the line in one to three cycles. Thereby high-speed fault clearing is obtained, which improves the power system stability. The auto-reclosing simultaneous reclosing signal is sent thereby simultaneous (1 to 3 cycles) reclosing of the circuit breaker is obtained. For simultaneous faults, carrier-current protection provides easy discrimination.
As per answer key "pilot protection" is true but there is mistake the right answer is "none".
The V-curves of a synchronous motor show relationship between Armature current (Ia) and Excitation current (If). The Inverted V-curves of a synchronous motor show relationship between power factor (pf) and field excitation (If).
In bias differential protection for transformer, There are two basic settings required to setup the percentage biased differential protection. 1. Minimum pickup 2. The slope.
The minimum pick-up covers the transformer magnetizing current typically 1-4% of transformer rating. A pick up of 0.2 to 0.3 times the TAP is recommended for general cases.
The slope is defined by determining the potential sources of differential current.
Class B trip curve: The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection. Hence, For 16 A current Type B MCB disconnect fault at 3*16 = 48 A to 5*16 = 80 A.