Electrical Machines
For a single phase capacitor start induction motor which of the following is valid?

  Rotation can be changed by reversing main winding terminals.
 Rotation can be changed by interchanging supply terminals.
 Direction of rotation cannot be changed.
 None of these.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are identical as 4% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 230.7 MW and 369.23 MW respectively
 generator 1 gets over load
 generator 2 gets over load
 200 MW and 400MW respectively

ANSWER DOWNLOAD EXAMIANS APP