MGVCL Exam Paper (30-07-2021 Shift 2)
A three-phase 400 V, 6-pole, 50 Hz squirrel-cage induction motor is running at a slip of 5%. The speed of rotor with respect to stator magnetic field and speed of the stator magnetic field with respect to rotor magnetic field are

-50 rpm, 1000 rpm
950 rpm, zero
950 rpm, 1000 rpm
-50 rpm, zero

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Which one of the following statement with respect to Aerial Bunched Cables (ABC) system is TRUE?

ABC system is not suitable for rural electrification which are situated in difficult terrain, hills, forests and coastal areas.
ABC system totally eliminates the fault on lines and thereby improving the quality of supply.
ABC system requires more clearance, insulators and high maintenance.
The overall cost of the ABC system is very high as compared to the bare conductor system.

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In transformer, a Sweep Frequency Response Analysis (SFRA) test will help detect ____

Moisture in the windings
Age of the insulation
Aging by-products
Movement / damage to internal components

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A 3-phase motor load has a p.f. of 0.397 lagging. The two wattmeter method used to measure power show the input as 30 kW. Find the reading on each wattmeter.

W1 = -10 kW and W2 = 40 kW
W1 = 10 kW and W2 = 20 kW
W1 = 5 kW and W2 = 25 kW
W1 = -5 kW and W2 = 35 kW

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
The magnitude of the generator earth-fault current is limited by

controlling field exciter
using higher rating CTs
inserting the stabilizing resistance in series with the relay
inserting suitable resistance in neutral grounding circuit

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP